Skip to Content

Thermostats

Operate your thermostats remotely, see what they report and whether a change is confirmed, and find every setting of the Milesight WT201.

Last updated on

Under ParkThermostats you see what your thermostats report and operate them remotely. Tillor works with the Milesight WT201, a thermostat that communicates wirelessly over LoRaWAN. A message can get lost on the way. That is why Tillor keeps what you want and keeps sending it until the thermostat confirms it. You can assign each thermostat to a terrain.

Before you start:

  • The thermostat reports through your own organisation's LoRa gateway, the receiver at or near your park. Reports that arrive any other way are not received. If you don't know whether your park has one, contact support.
  • You need the DevEUI of the device, the 16 characters on the label.
  • You need the View thermostats permission. Without it you cannot open the page.
  • To register, edit or delete you need Manage thermostats. Without it those buttons are greyed out.
  • To send settings and commands you need Control thermostats. Without it the buttons are greyed out, with the reason next to them. For installation commands you also need Manage thermostats.

You give these three permissions per colleague, see Permissions for thermostats.

Registering a thermostat

Required:Manage thermostats

Click Register thermostat

The button is above the All thermostats table.

Fill in the details

  • Name (required), for example the place where the device hangs.
  • DevEUI (required). You may leave spaces, colons and dashes in. If the number of characters is wrong, you see A DevEUI has 16 hexadecimal characters.
  • Terrain, or leave No terrain. To choose a terrain you also need the View terrains and the map permission.

Click Register

Tillor shows Thermostat registered.

A newly registered thermostat shows no values yet and has No report yet under Last report. The values appear after the device's next report. Tillor does not retrieve what it reported before you registered it. You can only operate it after that first report.

Where do you find a thermostat?

PlaceWhat do you do there?
The All thermostats tableAll thermostats with name, terrain, reported values, signal and last report. You search by name or DevEUI. The name opens the detail page
The side panelIn the table with Control thermostat (without the control permission View thermostat), on a terrain through ⋯ and Open details
The card on a terrainThe mini thermostat, ready to operate
The detail pageEverything about one thermostat. You get there through the name, through Open the detail page in the side panel or through an entry in the activity log

In the screenshot, ParkThermostats is green marker 1 and the table is marker 2. Hover over the ℹ icon for an explanation of the yellow symbol.

All thermostats table under Park > Thermostats, with the yellow symbol next to Woonkamer

The side panel shows the mini thermostat, the active alarms, Reported state, the five newest entries under Recent commands and the Open the detail page button.

All these pages update themselves when a report comes in or a command changes. Tillor only keeps the last reported state. There is no history or graph of the temperature.

The mini thermostat

Required:Control thermostats

The terrain page, the side panel and the Daily controls card on the detail page show the same mini thermostat. You operate it directly, without a window and without a button to confirm. When there is enough width, everything for one thermostat is on one line. On a phone and in narrow cards, such as the side panel, the parts are stacked.

Thermostats card on a terrain with two small thermostats; the orange line runs under the target temperature of Woonkamer
  • Next to the name you see what the device is doing now and the humidity, as far as reported, followed by the measured temperature. In the side panel and on the detail page, Room right now takes the place of the name.
  • With − and + you set the Target temperature 1 degree lower or higher, from 5 to 28 °C. The thermostat refuses a higher target temperature, so nowhere in Tillor can you send more than 28 °C (82 °F). If you tap several times in a row, Tillor saves only the last value.
  • In the Mode dropdown you choose Heat, Cool or Auto. Em. heat (emergency heating) only appears when the device reports that it supports it, or when it is already in that mode. Mode and temperature are sent together, in degrees Celsius.
  • In the Fan mode dropdown you choose Auto, On or Circulate.
  • The round power button turns temperature control on or off, without an extra confirmation. When it is on, the button has a green light at its top right. When it is off, the light is grey, the temperatures are dimmed and the thermostat shows Off. The device then no longer heats towards your target temperature.
  • On a terrain each thermostat has a ⋯ menu with Open details, Open the detail page and Remove from terrain. In the side panel and on the detail page that menu only appears when something in it is waiting to be confirmed. You find signal and last report under Reported state.

If you lack the control permission, or the thermostat has not reported yet, the buttons are greyed out and the reason is shown below them.

In Auto the thermostat both heats and cools to reach the target temperature. If the target is 12 °C while it is 24 °C inside, it starts cooling. If you only want heating, choose Heat.

Desired value and syncing

Tillor saves a setting you change right away as the desired value. You see it at once on the mini thermostat, even while the device knows nothing about it yet. Reported state shows only what the device itself last reported or confirmed.

  • Tillor sends a change at once. If you tap plus five times, the first value goes out at once and the last one with the next message. The values in between are dropped.
  • Settings that wait at the same time go in one message if they fit. The rest follows in a next message.
  • At least 15 seconds pass between two messages to the same thermostat. The next message also waits until the network has dealt with the previous one: with an acknowledgement, an error or after 90 seconds at most. Otherwise the network drops the new message.
  • If the network drops a message anyway, you see Delivery error and the command is back on Waiting to send. Tillor sends it again, a one-off action too: the device never received it.
  • Each setting has one desired value waiting and a newer one replaces the old one. Each weekly schedule slot, each plan, each child lock button, each group, each alarm type and each type of extra stage counts separately.
  • Mode and temperature are one setting. If you send only the mode while a temperature is pending, the new mode and that temperature go out together.
  • Wiring and O/B reversing valve are one setting, because the wiring table holds the O/B mode too. If you send only an O/B mode while wiring is pending, it goes into the pending table. New wiring replaces a pending O/B mode.
  • If you activate a plan, a pending temperature and fan mode lapse. If you choose a temperature or fan mode after that, the pending plan lapses.
  • If you set a value back to what the device reports and nothing had been sent yet, Tillor simply withdraws the change (Pending change withdrawn). If a value already sent can still change the device, Tillor does send the restored value.

How you see what is not confirmed yet

On the mini thermostat a thin amber line runs under each control that is not confirmed yet. If your device is set to reduce motion, the line stands still. A screen reader also says that the control is not confirmed yet. This is how you open the details:

  • Target temperature: tap the value between − and +.
  • Mode and Fan mode: open the dropdown. The details are below the choices.
  • Power, and settings without a control of their own such as Report interval: open the ⋯ menu. While such another setting is waiting, a line runs under ⋯ too.

In the All thermostats table and under All settings and commands, a yellow icon with two arrows takes the place of the line. The icon next to the name in the table stands for the whole thermostat. Click it for the same details.

You see:

  • Desired: what you asked for, and Device last reported: what the device said. The device does not report every setting: then it says the device does not report this setting;
  • Pending since, Last attempt: with the number of attempts, the last error if there is one, and Next attempt:;
  • the Discard change button.
Details of a target temperature that is not confirmed yet, with Desired, Device last reported, the attempts and Discard change

The line and the icon disappear as soon as nothing is pending.

When is a setting confirmed?

Tillor treats a setting as confirmed on one of these proofs:

  • the device answers the command (Answered by the device);
  • a report made after sending shows the requested value (Seen in a report). This works for mode and temperature in Celsius, fan mode, on or off and an activated plan;
  • the network reports that the device received the last message (Receipt confirmed by the network).

If the network does not report receipt, that tells you nothing: the device may have carried out the message anyway. A report with another value does not prove a failure either, because reports can arrive minutes late. After confirmation Tillor lets go of the desired value. If someone then changes something on the device itself, Tillor does not undo it. If the device confirms the mode, the temperature, the fan mode or on or off without a new report, Tillor copies that value into Reported state, unless a newer report is already there. A Fahrenheit temperature is then shown converted to °C, and a confirmed change of the wiring or the O/B mode is copied too.

If the device answers that something is not allowed or that the value is invalid, Tillor stops and the command gets the status Rejected.

Retries

Without confirmation Tillor sends the setting again: after 1 minute, then after 2, 5, 10 and 15 minutes, and after that every 30 minutes. There is no last attempt. Tillor keeps trying until the setting is confirmed or rejected, until you discard it or until a newer value replaces it. If sending itself fails, another attempt follows later too.

Tillor checks your permissions when saving and again before every message. If you lose the permission needed, Tillor withdraws the waiting command.

Discarding a change

With Discard change Tillor stops sending. What the device already received stays in effect. You need the same permissions as for sending the command. You can do this from the details behind the line or the icon, and in the command history. If the device answers a discarded change later anyway, Tillor shows that value as the reported state.

One-off actions

For a One-time action, repeating it could do harm or send outdated data. This applies to restarting, asking for a report now, synchronising the clock, switching relays directly, sending an external temperature and the three history commands (request, stop and clear). Tillor sends such an action once, in a message of its own, and never repeats it. If the network dropped the message before the device got it, Tillor does send the action again.

  • If no confirmation arrives within 15 minutes, it shows Unconfirmed. It may have been carried out anyway. Check that before you send it again.
  • Request a report is confirmed as soon as the requested report arrives; an acknowledgement from the network alone does not count. For Current status, any status report after sending counts, including a regular one the device would have sent anyway, and Tillor always takes it over. On a weak connection the thermostat first sends its overdue answers, so this can take a few minutes.
  • Restart is confirmed as soon as the device sends its start-up message after restarting.
  • If Tillor could not send it within 15 minutes, or sending failed, it shows Failed.
  • You can only discard it while it shows Waiting to send.
  • If you send an action twice, it goes out twice.

History is not stored

With Fetch history you ask the device for stored measurements, but Tillor does not store or show them yet. The device does not answer this command and Stop sending history in a way Tillor recognises, so expect Unconfirmed.

The detail page

At the top are the name, the DevEUI, the status, the number of changes not confirmed yet, the active alarms, the terrain, the last report, the signal and Registered on. The action menu has Edit thermostat and Delete thermostat. Below are these cards (on a phone the controls come first):

CardWhat is in it?
Daily controlsThe mini thermostat
Reported stateTemperature, target temperature, mode, status, humidity, fan mode, Fan activity, Last plan event, on or off, signal and last report
Device and alarmsAlarms and sensor errors, DevEUI, serial number, hardware and firmware version, LoRaWAN class, closed relays, connected wires and what the device supports
All settings and commandsAll commands, per group
Command historyEvery command with status, kind, time, attempts, proof or error, in pages
ActivityThis thermostat's activity log

The device sends most information about itself only when it joins the network. Until then you see a dash.

Detail page of a thermostat with the status and 1 change not confirmed yet at the top

Statuses in the command history

Command history with commands that are sent, confirmed, rejected, not confirmed and withdrawn
StatusMeaning
Waiting to sendSaved, not sent yet or sending is being retried
Sent, not confirmedTillor is waiting for proof
ConfirmedThere is proof
RejectedThe device refused
UnconfirmedAn action without proof within 15 minutes
FailedAn action that was not sent
ReplacedA newer value took its place. You only see these with Show replaced values
WithdrawnDiscarded by a colleague, or the requester lost the permission

All settings and commands

On the detail page, open a group under All settings and commands. A setting with one field you change in the list itself, with Send. For more fields click Set up. Where possible the fields start at the pending or reported value. The other fields have a starting value: check it before you send. For Wiring and O/B reversing valve Tillor chooses nothing for you. If the device has not reported its wiring and nothing is pending, you choose every terminal and the O/B mode yourself, based on the actual installation. A form you have not changed yet follows new values from the mini thermostat and the device. You add weekly schedule, plan content and D2D entries with Add entry.

All settings and commands with the Daily use group open

The Kind column says whether Tillor keeps sending the value (Setting) or sends it once (One-time action). With Installer setting the rules for installation commands apply.

Not everything has been tested on a device

It has been established that a real thermostat with firmware 1.3 carries out and answers Mode and temperature. Most other commands, and several settings together in one message, have not been tried on a real device yet. Check the result on site when it matters.

Daily use

CommandWhat does it do?ValuesKind
Mode and temperatureSet mode and target temperature together, in whole degrees.5…28 °C / 41…82 °FSetting
Target temperature (0.1°)Target temperature in °C with one decimal. Needs firmware 1.3.5…28 °CSetting
Mode onlyChange the mode without a temperature. Needs firmware 1.3.-Setting
On or offTurn temperature control on or off.-Setting
Fan modeChoose how the fan runs.-Setting
Activate a planApply a stored plan now. It replaces a pending temperature and fan mode.-Setting
Report intervalMinutes between reports, at least 5 because of LoRa airtime. The device does not report this setting.5…1440 minSetting
Request a reportAsk the thermostat once to send its status or plan.-One-time action

The report interval is at least 5 minutes. In Europe a LoRa device on 868 MHz may only transmit a small part of the time. With weak reception one report takes about 2 seconds, and reporting more often can exceed that limit.

Schedule and clock

CommandWhat does it do?ValuesKind
Synchronize the clockAsk the device to fetch the time from the network.-One-time action
Time zoneStandard time without daylight saving. Prefilled with your organization’s time zone.-Setting
Daylight saving timeWhen daylight saving time starts and ends. Week 5 means the last week of the month.±120 minSetting
Weekly scheduleOn which days and times a plan starts. Each slot (1-16) is stored separately.1…16, max. 6Setting
Plan contentsMode, fan, temperature and tolerance per plan.5…28 °C / 41…82 °F, 0.1…5, max. 4Setting

Time zone and daylight saving time are prefilled from your organisation's time zone. Check them before you send. If Tillor cannot read that time zone, for example because you may not view the organisation settings, the form says so. Choose or check the values yourself.

Comfort and protection

CommandWhat does it do?ValuesKind
Temperature dehumidifyDehumidify by cooling, with your own or the default tolerance.0.1…5 °CSetting
Fan dehumidifyHow long the fan runs to dehumidify.5…55 minSetting
Fan delayKeep the fan running after heating or cooling stops.5…55 minSetting
Circulate run timeMinutes the fan runs in Circulate mode. Needs firmware 1.3.5…55 minSetting
Humidity rangeMinimum and maximum humidity in percent. Needs firmware 1.3.0…100 %Setting
Humidity calibrationCorrect the measured humidity. Needs firmware 1.3.±20 %Setting
External temperature controlLet the thermostat use a temperature sent to it, with a timeout when none arrives.3…60 minSetting
Send external temperatureSend one measurement to the device.-40…80 °COne-time action
Temperature calibrationCorrect the measured temperature. A wrong value upsets control and freeze protection.±5 °CSetting, Installer setting
Temperature toleranceHow far the temperature may drift before the equipment switches. Too small makes it short-cycle.0.1…5 °CSetting, Installer setting
When an extra stage startsAfter how many minutes and at what difference extra heating or cooling starts.1…255 min, 0.1…10 °CSetting, Installer setting
Temperature alarmAt which temperature the device raises an alarm.-40…80 °C, 0…1440 minSetting, Installer setting
Freeze protectionBelow this temperature the device heats by itself. Turning it off removes a safeguard.1…15 °CSetting, Installer setting

Device and network

CommandWhat does it do?ValuesKind
Screen displayWhat the thermostat’s screen shows.-Setting
Measurement intervalSeconds between measurements inside the device.10…60 sSetting
Child lockOn = button locked. Unchanged buttons keep their state. This can lock users out.-Setting, Installer setting
Who is in controlWhether the thermostat itself or remote control decides.-Setting, Installer setting
Behaviour without networkWhat the device does when the network is lost.-Setting, Installer setting
Card switchWhat happens when a card is inserted or removed.-Setting
Multicast groupsWhich network groups the device listens to.-Setting, Installer setting
Device-to-device (D2D)Let devices control each other without a gateway.-Setting, Installer setting
D2D controller settingsWhich code this device sends per plan.max. 4, 0…1440 minSetting, Installer setting
D2D receiver settingsWhat this device does when it receives a code.1…16, max. 7Setting, Installer setting
RetransmissionLet the device send missed reports again later.-Setting
Retransmission intervalSeconds between retransmissions.1…64800 sSetting
Resend intervalSeconds between resent stored reports.1…64800 sSetting
History on the deviceWhether the device itself stores measurements.-Setting, Installer setting
Fetch historyAsk the device to send stored measurements. Tillor does not store them yet and cannot confirm this command.-One-time action
Stop sending historyStop the transfer of stored measurements. The device does not confirm this.-One-time action
Clear historyErases the measurements stored on the device. This cannot be undone.-One-time action, Installer setting
RestartRestarts the device. Heating and cooling are briefly interrupted.-One-time action, Installer setting

You enter start and end of Fetch history by the clock of your own computer or phone.

Installation

CommandWhat does it do?ValuesKind
WiringReplaces the whole wiring table. A mistake can damage the equipment.-Setting, Installer setting
O/B reversing valveWhen a heat pump’s reversing valve is energized.-Setting, Installer setting
Switch relays directlyOn = relay closed. Sent once; the device’s own control may change them again.-One-time action, Installer setting

Installation commands

Required:Control thermostats + Manage thermostats

Commands labelled Installer setting can change the wiring or behaviour of the installation, switch off a safeguard, erase data, restart or silence the device, or lock out users. They are not only in the Installation group. You need both permissions. After you fill them in, Tillor asks for confirmation, and the command is only saved with Yes, send.

Confirmation Send Freeze protection? with the buttons Cancel and Yes, send

A mistake can cause damage

  • Wiring replaces the whole wiring table. Every terminal you set to off is sent as not connected. If the table does not match the real wiring, the heating or air conditioning can be damaged.
  • A wrong O/B reversing valve makes a heat pump heat when you ask for cooling, and the reverse.
  • Switch relays directly has not been tested on a device. It can switch stages on at the same time or make the compressor short-cycle.
  • Turning off Freeze protection, calibrating the temperature or disabling an alarm can let pipes freeze without anyone noticing.
  • With child lock, remote control or the behaviour without network you can lock out people on site or leave a building without heating.

Have these commands carried out by someone who knows the installation and can check on site. Discarding does not undo what the device already received.

Alarms, sensor errors and activity

When the device reports an alarm, you see it on the detail page and in the side panel: Emergency heating timeout, Auxiliary heating timeout, Persistent low temperature, Persistent high temperature, Freeze protection or Temperature threshold. Most disappear when the device reports they are over. The two alarms about heating taking too long have no such end report and stay until another alarm replaces them. A sensor error (read failed or out of range) disappears when the sensor reports a value again. Tillor sends colleagues no notification about these.

In the activity log, and for an assigned thermostat also under the terrain's Events, you see registering, editing and deleting, every requested, discarded or withdrawn change, confirmed, rejected, unconfirmed and failed commands, and alarms and sensor errors. Individual attempts are not listed.

Editing or deleting a thermostat

With Edit thermostat you change the Name and the Terrain. No terrain removes it from its terrain. Click Save. You cannot change the DevEUI. If you replace a device, register the new one as a new thermostat. Without the View terrains and the map permission you cannot change the terrain. An assigned thermostat then shows Assigned terrain (no access to terrains).

With Delete thermostat you remove it from Tillor, after confirming with Delete. Its command history and pending changes disappear too. The device keeps what it already received and keeps working.

Problems?

See also

Was this page helpful?

On this page